Total Harmonic Distortion: History
Please note this is an old version of this entry, which may differ significantly from the current revision.
Contributor: Eng Editorial Office

Total harmonic distortion (THD) is a power-quality metric that quantifies the harmonic content present in an electrical voltage or current waveform relative to its fundamental component [1]. For a periodic waveform, THD is defined as the ratio of the root-sum-square of the amplitudes of all harmonic components—excluding the fundamental—to the amplitude of the fundamental component, usually expressed as a percentage [2]. The harmonics considered are integer multiples of the fundamental power frequency and arise from nonlinear loads and power-electronic converters [3]. THD may be evaluated for voltage (THD_V) or current (THD_I); a higher THD indicates a waveform that deviates more strongly from a pure sinusoid [2]. THD is distinct from total demand distortion (TDD), which normalizes harmonic current to the maximum demand current rather than to the fundamental [1]. Limits on harmonic distortion at the point of common coupling are established in power-quality standards, and THD serves as the primary figure of merit for waveform quality in such assessments [3].

  • total harmonic distortion
  • harmonic component
  • waveform distortion
  • power quality metric