2. LVRT Considerations
The growth in the penetration of grid-connected DPGS has led to changes in the ancillary services required by the GCs in order to guarantee the stability and reliability of distribution systems. To better understand the operation of DPGS during grid faults, this section presents the main aspects of voltage sags, reviews LVRT requirements in different GCs, and discusses some common strategies for voltage support.
2.1. Voltage Sags
A voltage sag is a short-time reduction in the RMS voltage value of one or more grid phases. They can be caused by short circuits, overloads, and the starting of large motors. Table 2 of IEEE Std 1159 categorizes different electromagnetic phenomena, including voltage sags
[26]. According to this standard, the magnitude of typical voltage sags is between 0.1 and 0.9 V
pu
. Nevertheless, some grid codes consider LVRT profiles from 0 to 0.9 V
pu
(e.g., the German code). Although magnitude and duration are the main characteristics of voltage sags, other features such as phase angle jumps and unbalance must be considered
[27]. In fact, the occurrence of symmetrical faults is rare (close to 2–3% overall
[28]). Therefore, most grid faults are asymmetrical, generating negative and zero sequence voltages in the network
[29,30].
2.2. Grid Code Requirements
GCs are a collection of technical specifications to coordinate the operation and integration of different power generators to the grid. They are imposed by the transmission and distribution system operators seeking to guarantee the stability and regulation of the system frequency and voltage
[31][32][31,32]. Over the last decade, the DPGS requirements have become more stringent in many countries due to the considerable rise in renewable energy generation
[33]. In this sense, GCs usually require the DPGS to stay connected to the grid during voltage sags. Moreover, maximum current and reactive current injection (RCI) are requested in order to support the voltage recovery. Once the fault is cleared, the DPGSs must resume active power supply
[34]. A voltage vs. fault duration profile is defined to consider the safety of the equipment.
In the same way, some GCs define a minimum RCI profile to provide voltage support
[35][36][35,38]. However, this requirement is based on the assumption that grid impedance is mainly inductive, which is not always valid (e.g., low-voltage microgrids have a mainly resistive impedance). In fact, many authors have found that the grid impedance must be taken into account to optimize the voltage support
[37][38][39][39,40,41]. Another feature to mention is that some GCs determine the RCI requirement considering the on-grid voltage reduction during the fault and the nominal power and current of the source, e.g., GCs of Germany and Colombia
[40][41][42,43].
2.3. Voltage Support Strategies and Secondary Objectives
Modern GCs must be adapted to overcome the challenge that the massive integration of renewable energies will pose to the power quality of electrical systems
[42][46]. For instance, the suitable characterization of the grid impedance
Zg
and the voltage support strategy selection play a relevant role in the voltage recovery. Camacho et al. has proposed three basic approaches of voltage support strategies: the first is an approach in which the positive sequence voltage support is maximized
[39][41]. In this case, all the phase voltages are raised equally by injecting active and reactive power only through the positive sequence. However, unfaulted phases can present a troublesome over-voltage due to the unbalance
[43][47]. The second is an approach in which the negative sequence voltage is minimized to reduce the unbalance between phases. Therefore, it is necessary to consume active power through the negative sequence, which is the major inconvenience of this strategy since a backup (EES) or an element to dissipate the power is required. The third is an approach that combines the two mentioned methods, and its goal is to maximize the difference between the positive and negative sequence voltages. According to Camacho et al., this strategy is the most convenient to restore the voltages to the values prior to the occurrence of the fault
[39][41]. Other control proposals have focused on maximizing the power delivered and the injection of currents, which result in a non-controlled voltage support
[19][21][42][19,21,46].
In addition to the voltage support, other LVRT secondary objectives such as minimizing the DC-link voltage oscillations, reducing harmonic components on injected currents, and mitigating power oscillations are also desired
[44][45][46][47][48][48,49,50,51,52]. To improve the inverter performance, achieving these secondary objectives is not a simple task, since the three main system restrictions must be considered: (1) maximum phase current limit, (2) maximum phase voltage limit, and (3) maximum DC-link voltage limit
[18]. In addition, there are regulatory restrictions such as the minimum amount of injected current, LVRT voltage profiles, and the maximum phase voltage allowed by the GC
[42][43][46,47]. Furthermore, the LVRT control strategy should also consider the type and severity of the fault, the grid characteristics, and the power generation and power curtailment scenarios. For these reasons, it is a common practice to organize the secondary objectives in a hierarchical control structure
[34].
3. System Description
3.1. Grid-Connected Inverter
The DC stage comprises the power source (renewable generation or storage systems). An optional DC-DC converter is mainly used to manage the voltage level and control the generated power
[49][53]. A DC-link capacitor
Cdc is used to balance the power exchange between the inverter and the DC-stage. A filter is implemented at the output of the three-phase inverter to reduce the high-frequency harmonics
[50][51][54,55]. The grid effect is usually modeled with a line impedance
Zg and a voltage source
Vg. Although not included in the scheme, some loads could be connected at the PCC, and
Zg may include the impedance of a power transformer between the inverter and the grid.
3.2. Control Loops
Briefly, during fault conditions, the reference current must be calculated to improve the voltage support while complying with the system restrictions. The synchronization algorithm estimates the grid frequency
ω and the symmetric components of the PCC voltages
[52][53][54][55][56,57,58,59]. The current controller tracks the reference signal and generates the pulses for the inverter
[56][57][60,61]. The generation control manages the power production at the renewable source.
According to the general criteria of the specialized literature, employing the full inverter capacity and a fast response are desired. It can be established that the synchronization algorithm and the current controller are mainly related to the reaction time of the inverter. One is responsible for sensing and obtaining the information of the PCC fault voltages, and the other implements the control’s actions through the inverter switching. On the other hand, generation control and reference current algorithms are responsible for exploiting the inverter’s full capacity.
4. Flexible Current Control Algorithms
Flexible current algorithms are selected for the calculation of current reference signals during voltage sags, since these allow the injection of different amounts of active and reactive powers via positive and negative sequences
[21]. Moreover, the flexible approach allows the manipulation of the power loops to avoid distorted currents and cancel power oscillations as well as other operational features.
4.1. Basic Formulation
First, some basic definitions are presented in order to state some principles of the flexible current control. For this strategy, the PCC voltages are decomposed in symmetric sequences on the
αβ0 frame, as shown in (
1), where
V+,
V−,
φ+, and
φ− are the amplitudes and phases of the positive- and negative-sequences voltages and
ω is the grid angular frequency
[23][34][23,34]. Moreover, the instantaneous active power
p and the instantaneous reactive power
q are defined by (
2) according to the
p-q theory
[58][59][62,63].
Using (
1) and (
2), the reference currents
i∗α and
i∗β can be expressed in terms of the reference powers
P∗ and
Q∗, as shown in (
3). Notice that the currents have a cosine term in the denominator that only appears if the PCC voltage is composed of positive and negative sequences.
Similar expressions can be obtained on the
dq0 frame
[60][61][64,65]. However, working in the
dq0 frame under unbalanced conditions does not bring additional benefits beyond those obtained by working in the
αβ0
frame, since the respective voltage components have a sinusoidal behavior in both cases
[59][63].
4.2. Fundamental Concepts of Flexible Control
The main characteristic of a flexible strategy is the ability to modify the control algorithm using scalar factors to achieve the desired control characteristics. The foundations of flexible control are presented by Rodriguez
[20] in the following control strategies:
-
Instantaneous Active Reactive Control (IARC);
-
Instantaneously Controlled Positive-Sequence (ICPS);
-
Positive-Negative-Sequence Compensation (PNSC);
-
Average Active-Reactive Control (AARC);
-
Balanced Positive-Sequence Control (BPSC).
The first formal introduction of the concept
flexible for current control in three-phase inverters corresponds to a variation of the PNSC strategy called Flexible Positive- and Negative-Sequence Control (FPNSC) proposed by the same Rodriguez et al.
[60][64]. Equation (
4) presents the reference currents for the PNSC strategy, where
v+ is the positive sequence voltage vector and
v+⊥ is an orthogonal version of
v+, led
90∘ by the original vector
[62][66]. The same definition can be applied to
v− and
v−⊥ considering the negative sequence instead of the positive one. Therefore, the voltage vector
v can be expressed as
v=v++v− (refer to Teodorescu et al.
[60][64] and Mehmet et al.
[61][65] for a detailed explanation).
Equation (
5) shows the reference currents according to the FPNSC. The most important remark is the introduction of the scalar factors
k1 and
k2, which explains why the FPNSC is considered a flexible control. Constants
k1 and
k2 are used to regulate the amount of active and reactive power injected through the positive and the negative sequences.
Notice that for the particular case in which
k1=k2=∣v+∣2/(∣v+∣2−∣v−∣2), (
5) will be equal to (
4), so PNSC corresponds to a specific design case of FPNSC. Although in some cases, the scalar factors
kihave a physical meaning, these are usually implemented as a control variable that allows accomplishing specific objectives during voltage sags. For this reason, any flexible current formulation usually has multiple variations. For example, (
6) shows an FPNSC control variation proposed by Mehmet et al.
[61][65]. In this case, the objective is to mitigate the active and reactive powers’ oscillating components. Therefore, Mehmet et al. have proposed only one scalar factor that is applied to the negative sequence voltage components
[61][65].
Another typical characteristic of flexible current algorithms is the possibility of avoiding distorted currents. This can lead to the appearance of an oscillating component in the injected powers. This approach is used in the AARC strategy of Rodriguez et al.
[20], where the RMS value of the grid voltages is used instead of the instantaneous values.
This expression corresponds to a general formulation. Indeed, if
k is selected according to (
8), the specific design case in (
3) is obtained.
Thus, the flexible approach allows setting the value of
k to achieve desired control characteristics, including the removal of the term on the denominator in (
3). To determine the appropriate values of
k, the injected powers are calculated by replacing (
7) into (
2).