2. Mechanism of Static Electrification
The charge separation at the pressboard and metallic surface contacts occurs due to the forced oil convection used for the heat transfer mechanism inside the transformers. The most basic model is “double layer stripping”, in which charge production occurs when the motion of the insulating liquid shears the double layer at the boundary between the liquid and solid phases. A number of hypotheses on the formation of the electrical double layer and its structure have been put forth by different researchers
[47,48,49][35][36][37] in its early stages. The solid–liquid coupling, which is apparently neutral, becomes polarized as a result of physico-chemical interactions when the insulating fluid is brought into contact at its interfaces. This causes the production of charges with a reverse polarity at the interface region. Intermolecular collisions are the primary mechanism of charge production in these interactions. As a result, the collision and impulse processes could result in space charge distribution in both the liquid and the solid insulation to create the electrical double layer (EDL), which is generally used to explain the electrostatic charging
[50][38]. The double layer consists of two regions; the first layer, often referred to as the fixed or compact layer, is located closer to the solid surface and can contain either positive or negative charges according to the electrochemical reactions. The ions within that second layer, often referred to as the diffuse layer, are allowed to migrate into the fluid. There are various studies that explained the mechanism of the charge creation of the liquid with metallic/pressboard insulation
[51,52,53][39][40][41]. According to a CIGRE report
[43][42], lowering the surface tension of the insulating liquid could reduce its electrostatic charging tendency upon contact with the pressboard material. The positive ions were drawn to the surplus electrons in the outer metallic structure and aggregated on the surface, while the negative ions were left back and transported by the insulating fluid far away from the compact layer.
The positive charges from the electrical double layer migrate toward the insulating liquid as a result of the streaming electrification phenomenon at the paper/pressboard insulation inside power transformers. This is explained by cellulose’s molecular structure
[54][43], in which the hydrogen ions present in the external structure of individual glucose units have a stronger affinity to the negative ions and thus build up the negative charges on the surface of the paper/pressboard insulation
[55][44]. Harvey et al.
[56][45] determined the charge density away from the double layer based on the relation between the Debye length and the diffuse sublayer thickness. The mass transport of an insulating liquid depends on the laminar flow for a lower Reynolds number, whereas turbulent flow determines the charge transfer for a higher Reynolds number. For the insulating liquid, it is inferred that the diffuse layer thickness is greater than the Debye length and that if the fluid results in a higher conductivity over its longer operation inside the transformer, the limiting case other than the former case can also occur, thereby increasing the streaming current. Despite the fact that these models were established for electrolytes, they later found application in solid–liquid interfaces in transformers. Variables such as temperature, permittivity, and concentration of ions in the insulating liquid affect the characteristics of a double layer. Compared to the electrolytes, the ionic concentration in the insulating liquid is very low when modeling the potential away from the interfaces. Walmsley and Woodford
[57][46] later constructed the pipe flow model to determine the current generated due to the laminar flow and determined the streaming current based on the assumption that the adsorption of ionic species was equal to the ions present nearer to the walls. It was finally concluded that different factors and models along with the rate of adsorption and diffusivity of positive and negative ions determined the magnitude of streaming current.
3. Factors Affecting the Streaming Electrification Phenomenon
The streaming current of an insulating fluid can be influenced by different factors such as velocity, type of fluid, applied electric field, temperature, and surface roughness. Since the rated capacity of transformers has increased in the recent years, the volume of oil used for cooling the transformer winding has also increased, resulting in a higher possibility of static electrification; hence, the various factors impacting the static charges are required to be clearly understood. Radwan et al.
[58][47] investigated the effect of frequency in the applied electric field, temperature, and velocity on static electrification and concluded that current existed under both energization and non-energization conditions. In addition, it has been noted that an increase in the applied electric field reduced the ECT of the fluid inside transformers. The change in the hydrodynamic flow pattern of the insulating liquid could modify the streaming current magnitude with variation in its velocity. This phenomenon could be related to the shear stress and diffusive sublayer thickness along with the friction existing between the insulating liquid and solid pressboard material
[59][48]. The velocity and streaming current follow both a linear and a log-linear relation at the interface between the insulating liquid and pressboard
[38][49]. The formation of oxidation byproducts in the insulating liquid with ageing can alter the flow mechanism governing the streaming current
[60][50]. Based on actual failure experiences, it is recommended to keep the oil flow rate for the heat regulating mechanism in a transformer unit below 3 m/s
[61][51]. Transformers can operate at very high temperatures, which have an adverse effect on the paper/fluid insulation’s propensity for charging tendency. In fact, the magnitude of the streaming current develops exponentially in accordance with temperature; these characteristics are mostly governed by the ionic mobility and diffusion coefficient
[62][52]. Additionally, as a result of the fluid’s turbulent motion at high temperatures, the charge carriers collect on the pressboard material. The alternate dielectric fluids age more rapidly than the existing mineral oil with a discernible difference beginning at a temperature of about 80 °C. It is inferred that self-contamination of the liquid and leakage of ionic substances from solid materials are the causes of ageing impact on electrostatic charging, which is more severe in the presence of copper and oxygen
[63][53]. The surface roughness of the pressboard insulation inside the transformer scratches and non-uniform surface increased the magnitude of streaming current to 10 times higher than in the uniform condition. Thus, each of the aforementioned elements has an individual or combined effect on the streaming current.
4. Streaming Current in Different Insulating Fluids
4.1. Mineral Oil and Silicone Oil
Mineral oil has been widely used in transformer applications for a very long time due to wide research on its insulation properties. This oil, which is derived from crude petroleum, involves a refining process that can be either naphthenic or paraffinic in nature
[12]. Mineral oil was used in experiments on static electrification after major fire hazards were found in transformers in 1980. Kedzia and Brozostek
[64][54] studied the static electrification of transformer oil as a measure of its ageing parameter and found that the impact of pipeline materials led to different leakage currents. In addition, the streaming phenomenon showed a better sensitivity to ageing characteristics and could detect the change in the insulation behavior at its early stages. The mineral oil was further investigated for ECT with transient characteristics
[42][55] in which the migration of water and air injection toward the pressboard interface played a major role in the charging current. The aromatic additives present naturally in mineral oil provided a lower streaming current during the initial transformer operation, but at the same time, the longer ageing of the oil could lead to adverse fire hazards
[65][56]. The static charges in power transformers can lead to partial discharges due to the accumulation of potential on the surface of the pressboard insulation, which usually occurs when the rate of change in the incremental charge is higher than the rate of charge leakage
[66][57]. The impact of free radicals generated in the oil during transformer operation not only affects the physio-chemical properties, but also the static charges with a polarity reversal observed under localized thermal stress
[67][58]. The diverse compounds present in the mineral oil were tested using accelerated thermal ageing under laboratory conditions in which the oxygen and copper catalyst that led to the formation of peroxide was found to be responsible for an increased ECT with ageing
[68][59]. Paillat et al.
[69][60] found that the effect of modifying cellulosic pressboard insulation with fibers from cotton and crystalline reduced the ECT of mineral oil but starch addition and laser-plasma treatments had no desired positive effects. The different factors (speed, temperature, rotation time, and electric field) studied in the electrification of mineral oil indicated that the interfacial charge density affected the breakdown strength
[54][43]. The thermal ageing of mineral oil assessed using turbidity and spectrometric analysis provided a good correlation with the ECT
[70][61]; the dissolved gases formed during the ageing process affected the magnitude of the streaming current. Silicone oil was measured for its streaming electrification using different insulating materials and the researchers concluded that a combination of silicone oil with Nomex paper could be a suitable interface to reduce the impact of ECT in transformers
[71][62]. In addition, the electric charge of silicone was negative and smaller in magnitude compared to the positive charges observed in mineral oil. Similar research performed on the silicone oil
[72][63] indicated a maximum current at 100 °C irrespective of changes in the kinematic viscosity and the silicone oil was less likely to cause a breakdown due to streaming behavior compared to mineral oil.
4.2. Ester Fluid
The alternate dielectrics from ester initially gained importance at the distribution level; now, the increased data available on these fluids regarding its dielectric performance has made them viable for power transformers. Ester fluids were tested for its static discharges initially using a sensor-based prototype along with simultaneous measurement of the charge accumulated at the pressboard surface and the leakage current
[73][64]. Although the ester fluids showed a higher current generation, the increased conductivity could remove the charge accumulated on the pressboard insulation and thus limited the potential build-up across the spacers. This initial study on ester fluids could not determine the reason for the charge generation and concluded that it could be due to conductivity, viscosity, or physio-chemical reactions at the interfaces. Later, the rotating disk method was adopted in a synthetic ester fluid; its performance after being subjected to thermal ageing with the presence of paper and copper was reported
[74][65]. The analysis in the study revealed a lower charging current in synthetic ester upon ageing compared to mineral oil with a higher relaxation time due to its higher volume resistivity. The pipe flow model investigated in a synthetic ester fluid by a similar research group resulted in identical conclusions made when using the rotating disk model
[75][66]. Talhi et al.
[60,76][50][67] used the spinning disk system to compare the charging tendency between ester fluids and mineral oil. This technique provided a higher charging current with synthetic ester compared to mineral oil and showed a completely different result from the previous methods. The parameters influencing the ECT upon ageing were moisture, dissolved gases, and oxygen diffused in the fluid. The impact of different solids on the ECT in synthetic ester fluid
[77][68] was studied while considering the flow velocities and temperature and showed a higher magnitude than mineral oil
[78][69]. The type of solid pipe (carbon, aluminium, cellulose, or aramid) used for the flowing of the insulating liquid also governed the streaming electrification. The fluid used in the transformer had its interface not only with pressboard insulation, but also with other metallic contacts; the streaming current was compared between mineral oil and natural ester using fiber glass/copper and pressboard/copper
[79][70]. Among the different interface materials, the usage of pressboard/copper showed a higher ECT for natural esters. However, at higher temperatures, the charging tendency of mineral oil exceeded that of the natural ester fluid, indicating that impurities formed in the fluid at higher temperatures could modify the streaming phenomenon. The above research provided an idea that ester fluids are more superior to mineral oil when considering the ageing phenomenon
[80][71]. The comparison of streaming current between synthetic ester and natural ester showed an ECT that was five times higher in the former compared to the latter
[81][72]. In addition, the rate of change in the charge accumulation was very minimal compared to rate of transfer in the charges for both the ester and mineral oil. Based on an evaluation of the charge accumulated on the pressboard material from the ECT, the magnitude level was the same for ester fluid compared with mineral oil and thus could be a promising insulant in transformers up to 500 kV.
5. Effect of Additives on Streaming Current
Over the past century, a number of additives have been claimed to improve the physio-chemical and dielectric properties of an insulating liquid. These included different substances such as inhibitors, antioxidants, and electron scavengers, which reduce the partial discharge inception voltage and the charging tendency of the fluid and improve the breakdown voltage
[99][73]. The different additives (Irgamet 39, benzotriazole, and C60) were used mostly for the reduction in the electrostatic charging tendency in power transformers. Both benzotriazole and Irgamet 39 are triazole-type derivatives of benzene except with a change in the group attached to the external nitrogen ring
[100,101][74][75]. In addition to reducing the static charges of insulating fluids, these two additives function as a passivator around the copper and pressboard surface for the diffusion of sulfur compounds
[102][76]. C60 is a type of fullerene that is spherical in shape with 60 carbon atoms providing excellent heat conductivity and lubrication performance
[103][77]. Apart from the above-mentioned additives, the suppression of static electrification was initially tested using ionic and non-ionic additives
[104][78]. Based on the experimental results, it was concluded that the chemical structure of the additive played a major role in the static charges, with non-ionic additives containing a polyethylene group showing the lowest streaming current. Further, additives such as alkylbenzene and benzotriazole
[105][79] were investigated for the streaming current in large power transformers. The tests were conducted in the presence of oxygen, which provided a better reduction in the ECT for both of the additives, but the researchers were unsure about their compatibility and reliability with other materials in transformers. The conductivity of an insulating liquid depends on the amount of positive and negative ions present in the compound. Similarly, the streaming current of an insulating liquid depends on the quantity of dissociated ions; thus, a relation was postulated between the current formed at the interface with the activation energy required for the ionic transfer
[106][80]. In the study, it was observed that the streaming current was a function of ionic charges present in the bulk liquid and activation energy involved in the transfer of ions to interfaces. Mohamed EL-Adawy et al.
[107][81] studied the physio-chemical reaction at the interface between the liquid and pressboard material using OLOA 218 and OLOA 219, which led to a modification in the amplitude and polarity reversal of the streaming current. This variation could distinguish the reagent of fluid with the solid material for the streaming current. The optimum concentration of benzotriazole (BTA) of 20 ppm added into the liquid decreased over a longer time interval due to its diffusion into the pressboard material. The streaming current measured under a pressure gradient of 1.85 bar was reduced by almost four times after creating a flow period of 5 h toward the pressboard material
[108][82]. The impact of BTA caused a change in the physio-chemical interaction occurring at the interface along with its dissociation in the insulating liquid
[55][44]. The BTA molecule decomposed into a triazole ring and hydrogen ion upon its addition to the fluid. The unsaturated double bonds present in the structure of the BTA molecules upon dissociation reacted with paper/pressboard insulation, releasing extra electrons and attracting positive ions from the surface, which caused equal amounts of negative ions to diffuse into the liquid
[109][83].
6. Effect of Electric Field on Streaming Current
There have been numerous investigations and databases created for the streaming current of an insulating fluid under an unenergized condition. So, a large experimental model was developed by Westinghouse with shell-type transformers with a 240 MVA capacity in which the static electrification phenomenon was understood. The energization of the insulating liquid could affect the streaming current, which, along with different flow conditions, governed the magnitude of the charge generation
[62][52]. The streaming current under the energization condition increased 1.5 to 2 times when performed using 60 Hz electric stress
[115][84]; the impact of AC voltage stress was not considered, and hence the observed results might have varied when the transformer was energized. Later, Miyao et al.
[116][85] investigated the effects of AC and DC fields on the streaming electrification in transformer oil; they found that lower field regions under AC voltage were influenced by the apparent charge distribution and that for higher fields, the acceleration in the charge was observed at the interfaces. The polarity of the DC field had an influence on the streaming current with a negative conduction current affecting it in lower fields and a positive conduction current affecting it in higher fields. A highly charged fluid in the transformer reached the top of the tank, causing a severe failure. Although the intensity of the discharge had a very minimal effect on the ECT, the situation could become worse for higher discharge intensities
[30]. The impact of DC fields on the streaming current was further investigated by Wu and Jayaram
[31], who inferred that a positive DC field always enhanced the current magnitude and that in the case of a negative DC field, the current was a function of the field. The calibration and development of the streaming current in a cellular duct of a transformer winding was conducted with a boundary layer and explained the charge transfer mechanism as a function of electric field under different flow conditions
[117][86]. Metwally investigated the effects of solid insulation material on the streaming current of transformer oil
[118][87]; ageing conditions were observed a higher ECT under both AC and DC fields with polarity reversal dominating at lower temperatures. In addition, the conduction in both the fields was inferred to be a function of the square root of the applied voltage. The streaming current was studied in pressboard/paper insulation through a thin insulating pipe that indicated the leakage current from the positive to negative electrode for DC field conditions, with asymmetry and electrophoresis affecting the streaming current under an AC field
[119][88]. Since electrification results with the energization of AC and DC fields became predominant, the impact of mixed fields on the streaming current was studied by Metwally
[120][89]. The level of harmonics had a significant effect on the streaming current; a combined effect of the magnetic field and the electric field increased the ECT of the transformer oil. The AC-superimposed DC voltage in the transformer oil could increase the streaming current due to negative ion dispersion toward the interface
[121][90]. Thus, the different fields can affect the streaming phenomenon of insulating liquids in power transformers.