The national electricity market (NEM) of Australia is reforming via the rapid uptake of variable renewable energy (VRE) integration concurrent with the retirement of conventional synchronous generation. System strength has emerged as a prominent challenge and constraint to power system stability and ongoing grid connection of VRE such as solar and wind.
SS has emerged as a technical challenge confronting Australian power systems transforming to a low-carbon future.
Historically, SS in the NEM has predominantly been provided as a byproduct when energy is produced by large synchronous generators, and was abundant in many parts of the network.
Issue | Description | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Inverter-based resource stability | IBR requires a minimum SS to remain stable and maintain continuous uninterrupted operation. Different types of converters use different strategies to match their output to the frequency of the system while maintaining voltage levels and power flows. In a weak system, this can lead to:
|
|
|
|
| ||||||||||
| Synchronous machine stability | Low SS can affect the ability of remote or small synchronous machines to operate correctly, resulting in their disconnection during credible contingencies. | |||||||||||||
Synchronous Generation Centres |
|
|
| Operation of protective equipment | Protective equipment within power systems works to clear faults on only the effected equipment, prevent damage to network assets, and mitigate risk to public safety. In weak systems:
|
|
| ||||||||
Voltage management | Strong power systems exhibit better voltage control in response to small and large system disturbances. Weak systems are more susceptible to voltage |
Historically, there have been several noncredible contingency events that led to blackout or islanding due to the arising challenge of generation mixture in the NEM [19][17]. The Australian Energy Market Commission (AEMC) has revised electricity rules more frequently since 2016 to ensure system security and stability.
As shown in Table 2, the newest framework as per Clause 5.20.C National Electricity Rules (NER V156) [22][18] requires that AEMO set fault level nodes and calculate minimum three-phase fault level amounts required at each of the nodes as a kind of proxy for SS provision across the NEM. According to [23][19], AEMO must publish an annual report regarding system strength requirements and including projections for SS amounts and any declared shortfall for the next five years. Correspondingly, local transmission network service providers (TNSP) or jurisdictional planning bodies are responsible for making and procuring available services to address the SS shortfall as directed by AEMO. TNSPs are required to provide SS service in each region and identify any fault level shortfall as part of the NTNDP. In addition, newly connected generators must remediate their own impact with a “do no harm” requirement for connecting to the network. If the connection of generators that demand system strength is the cause of some of these costs being incurred such generation should also share some costs of these services, as reflected in the system strength mitigation requirement (SSMR) [24][20]. The SS charge has been introduced to the SSMR to coordinate the mitigation option. The charge is made up of the three factors shown below:
where the first component, unit SS price, is fixed for a five years interval; the second, SS locational factor, is related to the site-specific electrical distance at the POC, indexed with a five-year interval; and the last, SS quantity, represents the amount of SS service used by connection as fixed at the time of connection.
Synchronous Generation Centres | |||||||||||||||
|
|
|
|
Participant |
---|
Obligation |
---|
Australia Energy Market Operator | Determine the level of SS required for existing generators to operate stably |
Transmission Network Service Provider | Respond to a shortfall in SS within their network |
Connecting Generator | Connecting generators must ‘do no harm’ to existing generators, loads, or network equipment. Remediate any ‘harm’ to existing levels of system strength |
DNSP | Not considered yet |
AER | Australia energy market regulator |
AEMC | rule maker |
Fault Level Nodes Selection Inputs | |
---|---|
Metropolitan Area | |