PCM-Enhanced Buildings: Comparison
Please note this is a comparison between Version 2 by Rita Xu and Version 1 by Mohammed M. Farid.

The incorporation of phase change materials (PCM) in buildings has the potential to enhance the thermal efficiency of buildings, reduce energy cost, shift peak load, and eventually reduce air pollution and mitigate global warming. However, the initial capital cost of PCM is still high, and thus the establishment of a control strategy has become essential to optimize its use in buildings in an effort to lower investment costs.

  • phase change material
  • ON/OFF control
  • conventional control
  • intelligent control
  • buildings

1. Introduction

In recent years, population growth and industrial developments have resulted in a dramatic increase in energy consumption and greenhouse gas emissions. Figure 1 and Figure 2 show the rising trend of total energy consumption [1,2][1][2] and CO2 emissions [3], over the period between 1990 and 2019, respectively. According to the statistics of the U.S. Energy Information Administration, today’s rate of energy consumption is higher than its production, which is a cause of significant concern about the future availability of energy [4]. Studies confirm that the building sector is one of the most prominent energy consumers, worldwide. Almost 50% of energy is consumed in buildings in the USA [5], 40% in Europe, and 36% worldwide, of which space heating and cooling account for approximately 50% [6]. Thus, energy demand with an annual rate of increase of 2.3% has created awareness towards the need to use renewable sources of energy to reduce climate change and achieve sustainable development [7].

Figure 1. World’s total energy consumption by sector over the period between 1990 and 2019 [1,2].

World’s total energy consumption by sector over the period between 1990 and 2019 [1][2].

Figure 2.

World’s total CO

2

emissions from 1990 to 2019 [3].

Significant attention has been directed to manage the growing energy demand, energy security, and energy consumption pattern, especially by heating, ventilation and air conditioning (HVAC) systems, and their associated grid loads [8]. In many parts of the world, for example, direct solar radiation is a promising source of energy as it is free, renewable, unlimited, and eco-friendly. In solar heating applications, a building can either absorb solar energy passively without requiring any mechanical and electrical devices [9] or use of auxiliary equipment to efficiently convert solar energy to thermal or electrical energy [10]. Solar energy varies according to the time of the day, season, climatic conditions, and other factors. Generally, solar radiation flux reaches its maximum level at midday, while it diminishing to zero at sunset. To tackle this limitation, thermal energy storage (TES) systems allow excess heat or cooling energy to be stored for later use. TES or enhanced thermal mass is that property of materials that defines their ability to absorb, store and release heat according to the surrounding conditions. TES increases the overall efficiency and reliability of heating and cooling by providing thermal comfort and indoor temperature stabilization. Additionally, it reduces the pollution, and CO2 emission associated with fossil fuel use [11].

Thermal energy is stored in materials through sensible heat by changing the temperature of material [12], latent heat by altering the phase of material within a narrow temperature range [13], and through reversible thermochemical reactions [14]. Among different TES systems, latent heat thermal energy storage has attracted wide attention due to its ability to store a large amount of energy per unit volume, isothermally, by using phase change materials (PCMs). Studies show that PCMs can store heat per unit volume 5–14 times more than sensible heat storage materials [15]. Figure 3 compares the thickness of building construction materials required to store the same amount of energy (the energy required to increase the temperature of 240 mm concrete from 20 °C to 30 °C). Thermochemical energy storage materials are also technically complex and challenging to apply, and hence require higher capital expenditure [16].

Figure 3.

The thickness of building materials required to store the same amount of energy [17].

PCMs are divided into organic materials, such as paraffin and non-paraffin-based compounds, inorganic materials, such as hydrated salts and metallics, and eutectics [18], which are a mixture of components with a freezing point less than the individual components. Figure 4 illustrates the classification of the PCMs [19]. All PCM types have some advantages and disadvantages [20] which are summarized in Table 1.

Figure 4. Classification of phase change materials (PCMs) [19].

Table 1. Advantages and disadvantages of different type of PCM [20].

An ideal phase change heat storage material should exhibit some desirable thermodynamic, chemical, kinetic, and economic properties. Following are some of the criteria used to select the proper PCM [13,18,21][13][18][21].

Thermodynamic properties:

-

A melting point within the temperature range of application;

-

-

High latent heat of fusion per unit mass and volume, so that a smaller amount of material is required to achieve a certain energy storage capacity;

-

-

High specific heat capacity to take advantage of significant sensible heat storage effect;

-

-

High thermal conductivity, so that heat could be absorbed or released faster;

-

-

Small volume changes during the phase transition;

-

-

Congruent melting;

-

-

Small vapor pressure.

Chemical properties:

-

Experiencing reversible freezing/melting cycle;

-

-

Chemical stability which means being non-corrosive and not being decomposed during the freezing/melting cycle;

-

-

Non-toxic and non-flammable.

Kinetic properties:

-

High nucleation rate to avoid supercooling;

-

-

High rate of crystal growth to meet demands of heat recovery from the storage system.

Economic properties:

-

Cost-effective;

-

Available in large quantities.

2. Different Control Strategies Applied to PCM-Enhanced Buildings

Different control strategies have been applied to PCM-enhanced buildings to control the operation of the mechanical and electrical devices and hence ensure indoor comfort and minimize electricity consumption, cost associated with energy consumption, and CO2 emissions. Control strategies can be divided into different categories such as ON/OFF control, classical control (P, I, PI, PID, etc.), adaptive, optimal and predictive control, and intelligent controls [68][22], which are discussed thoroughly in the following subsections.

2.1. ON/OFF Control

ON/OFF control, also known as hysteresis control, is the simplest feedback control method that switches the manipulated variable between two states of ON or OFF, abruptly. ON/OFF controller uses the upper and lower bound of the objective variable to regulate the process within the given thresholds [70][23]. As an example, Gholamibozanjani and Farid [71][24] implemented an ON/OFF control strategy in an experimental hut equipped with PCM storage to ensure its thermal comfort in different seasons of the year. In winter, for instance, the PCM storage system was ON if the PCM temperature was higher than the indoor room temperature; otherwise, an electric heater was automatically started to maintain the comfort condition. Such controllers can drive the manipulated variables from a fully open to a fully closed state and vice versa over a specified period. Solgi et al. [72][25] implemented a night ventilation technique to lower the summer cooling demand of an office building in hot-arid areas. The night ventilation was scheduled to automatically start once the outdoor temperature dropped below 30 °C and to stop at 7 a.m., thus solidifying the PCM using the coolness available at night and then melting it to absorb heat during the day.

Although the ON/OFF control method is inexpensive, simple and easy to implement, it is not able to control dynamic processes with time delays [73][26] as it is either fully ON or fully OFF, and hence causes chattering in the control output. In fact, a proper hysteresis is required, which otherwise would make output deviate from the temperature set-point. Moreover, considerable signal noise is introduced to the measuring process, which results in inaccurate output measurements [74][27].

Kenisarin and Mahkamov [75][28] performed a review on controlling thermal comfort in small laboratory models and real-size test rooms enhanced with a PCM applied passively. Implementation of such control strategies aims to meet different primary objectives such as energy-saving, electricity cost-saving and peak load shifting while maintaining indoor thermal comfort; these are discussed in depth in the following subsections.

2.1.1. Overall Energy Consumption Reduction

Application of control strategies to a building can enhance its energy efficiencies and hence reduce the pollution associated with fossil fuel consumption used for power generation [76][29]. Chen et al. [77][30] examined the effect of combined night ventilation and thermal energy storage using PCM to reduce the energy consumed for space cooling in an office building. In their simulation-based study, a typical south-facing office room located in Beijing, China, was considered as a base case for their study; also, a control algorithm was implemented to regulate the indoor temperature. Based on the control algorithm, during the period from 8 a.m. to 6 p.m. (office hours), fresh air was always provided for the occupants. However, if room temperature exceeded the higher bound of comfort level by 1 °C, the PCM started cooling down the room. If room temperature exceeded the comfort level by 2 °C, and the 3-min shut-off period of the air conditioner was met, the air conditioner would hence start. During the night (from 6 p.m. to 8 a.m.), outdoor air was introduced to the storage unit to solidify the PCM to be used during the following day. The results showed that it was possible to achieve energy saving between 16.9% and 50.8%. Another example of night ventilation, based on the ON/OFF control algorithm showed reduced electrical energy consumption and as a consequence reduced CO2 emission [78][31].

In addition, by using a simulation tool, Transient Systems (TRNSYS), Wang et al. [79][32] proved that the implementation of a control strategy into a ground heat pump system in conjunction with PCM reduced electrical energy consumption in Xi’an (Humid Subtropical Climate in China). They showed 7.9 °C improvements in the average temperature of the heat pump with an increase in its average coefficient of performance (COP) from 3.4 to 3.8.

Table 2 summarizes the studies carried out on the application of ON/OFF controller in combination with PCM for the sake of reducing energy consumption and indoor temperature fluctuation. In this table, type of PCM used and its integration place, the reason for using a controller, scale of the study, type of study (experimental/numerical) and energy benefits were reported.

Table 2. Application of ON/OFF controller in PCM-enhanced buildings for energy consumption reduction.

2.1.2. Cost Saving

Integration of PCMs into buildings can serve to make energy-savings by storing solar energy for later use (heating) or by storing free cooling available at night in summer (cooling). Changing the electricity consumption pattern by end-use customers, on the other hand, plays a significant role in managing demand resources and cost-saving. In this regard, postponing the use of electricity during high wholesale market price periods and using it during cheaper hours is an effective approach to demand responses [69][46]. For example, in 2015, Barzin et al. [93][47] initiated a “price-based” control strategy in a PCM-enhanced building for space heating. They examined the potential of PCM technology in conjunction with underfloor heating in an office-size building at the “University of Auckland,” New Zealand. Figure 5 shows a general view of the data acquisition and control system applied to their experimental building. According to their control system, the underfloor heater was switched ON or OFF based on the online dynamic electricity price, price constraint, and desired room temperature, which algorithm is shown in Figure 6. The experimental measurements over five days in winter confirmed a total energy-saving of about 18.8% with a corresponding 28.7% of cost-saving, while the highest energy and cost-saving were equal to 35% and 44.4%, respectively.

Figure 5. Control system used in Barzin et al. study [93][47].

Figure 6. The control strategy applied to the huts of the University of Auckland for passive space heating [93][47].

Barzin et al. [6] also implemented a price-based control strategy for space cooling in summer, based on the weather conditions in Auckland which has a “Marine West Coast Climate”. Two similar experimental huts (interior dimensions 2.4 m × 2.4 m × 2.4 m), each constructed with light-weight materials and provided with 1 m × 1 m north-facing windows, were used to perform some experiments. One of the huts, referred to as “hut 1”, was considered a reference for experiments, and its walls and ceilings were finished with 13 mm gypsum boards. While the other hut, referred to as “hut 2” was finished with PCM-enhanced gypsum boards. The PCM used was PT20 with a narrow melting temperature of about 20 °C. Both huts were also equipped with air conditioning units. The aim of the “price-based” control strategy was to keep the indoor room temperature in summer between 17 °C and 19 °C during off-peak periods (when the online price was lower than price constraint), and between 24 °C and 26 °C, during on-peak hours (when the online price was higher than the price constraint). An air conditioner was used to provide the comfort condition, but 100% more energy was consumed in hut 2 compared to hut 1, over 6 days. Therefore, they tried applying night ventilation in combination with air conditioning during the daytime, showing an energy-saving of about 73% over one week.

2.1.3. Peak Load Shifting

Peak demand or peak load is referred to as the maximum demand over a specific billing period. Peak demand usually varies for different types of buildings. Usually, residential users are charged based on a single tariff rate and only recently some electricity suppliers provided a variable electricity rate for the sake of peak load shifting. The incentive of peak load shifting for residential users would be electricity cost saving as well as improved quality and reliability of power. Peak demand for a commercial building lasts for a short period; however, it counts for half of the overall electricity bill. Hence, peak load shifting can not only reduce the peak demand, but it also saves substantially on energy costs [94][48]. Studies show that peak load management can lead to $10–$15 billion cost-saving in the US market annually [95][49]. Figure Figure 77 illustrates the schematic view of a typical peak load shifting in summer.

Figure 7. Overall view of a typical peak load shifting [94][48].

There are other benefits from offsetting the peak load including the reduction of generation of electricity from non-renewable energy sources during periods of peak demand and resilience during times of power outages. Even if a renewable source of energy is used, its generation during peak demand is not guaranteed as it may be cloudy, for instance, when solar energy is used. Power generation companies usually design their systems based on average load. Thus, any peak demand requires auxiliary equipment which causes extra cost, maintenance, and pollution that can be prevented by peak load shifting. On the other hand, as power generation facilities age, equipment failures accelerate, and as the demand for power increases over the years, existing plants have trouble meeting load requirements. To compensate for this, a plant may elect to install an energy storage system that can be charged when demand is low and discharged when demands cannot be met by the primary generation source.

Shifting of peak load also reduces losses in the transmission and distribution systems and hence carbon emission will be reduced as a result of more efficient operation of power plants and less load variability.

Studies show a significant potential of PCMs in peak load shifting [96][50]. In most cases, there is either no control strategy or only an ON/OFF control strategy. However, the best results have been achieved with control strategies. Peak load shifting control applied to PCM-enhanced buildings can be divided into two groups based on PCM integration into either the building envelope or into HVAC systems.

In terms of PCM incorporation into the building envelope, Khudhair and Farid [97][51], proved the concept of peak load shifting by charging the PCM-enhanced gypsum boards using electrical energy during low-demand hours to be used during high-demand hours. In Canada, Bastani et al. [98][52] also evaluated the effect of an ON/OFF control on shifting heating peak demand of a real bungalow building integrated with PCM wallboards. Through a numerical study via TRANSYS, they considered five different room set-point temperature ranges such as 20 °C–25 °C, 19 °C–24 °C, 18 °C–23 °C, 20 °C–24 °C, and 20 °C–23 °C. The PCM melting and solidification temperatures were 23 °C and 17 °C, respectively. Based on their control strategy, during the off-peak hours from midnight until 5:30 a.m., a heater was set in operation to charge the PCM and hence maintained the room temperature at the upper bound of comfort level. Then, during peak hours from 5:30 a.m. to 9:30 a.m. the heater was OFF, but PCM kept the room temperature at the lower bound of comfort level. Results showed that larger indoor temperature swings resulted in a higher total daily energy consumption and a lower peak load shifting. Moreover, setting the operational temperature range closer to the melting and solidification temperatures of PCM, 18 °C–23 °C, for instance, resulted in better utilization of the PCM and a longer period of peak load shifting. Barzin et al. [99][53] conducted another price-based control strategy for peak load shifting in winter. In their study, two experimental huts were finished with 13 mm gypsum boards and equipped with identical electric heaters. However, one of the huts was internally lined with DuPont PCM wallboards having a melting temperature of 21.7 °C. The indoor air temperatures were planned to be kept between 21 °C and 23 °C during off-peak hours, and between 17 °C and 19 °C, during peak hours. The thermal performance of the hut was then compared. Table Table 33 summarizes the energy and cost-savings of the PCM-enhanced hut over six days, based on the weather conditions in Auckland.

Table 3. Power and cost-savings for six days of winter [99][53].

Peak load shifting can also be achieved through the integration of PCMs into heat exchangers [100][54]. For instance, the potential of an air-PCM heat exchanger unit for peak load shifting was investigated by Stathopoulos et al. [101][55] in France. In their experimental work, a heat exchanger unit composed of a set of plates containing paraffin having a melting point of 37 °C (Figure 8) was integrated into a ventilation system in a test cell, known as “Hybcell”. Considering thermal comfort and indoor air quality of Hybcell, the aim was to reduce peak demand, particularly during late afternoon periods in winter. To this end, a preliminary control strategy was introduced to evaluate the capability of the system for peak load shifting. An electrical resistance heater was also provided to charge PCM and warm up the test cell during off-peak hours, then the PCM was discharged during peak hours. The experimental measurements showed that the proposed design allowed peak load reduction while the Hybcell met the thermal comfort requirement of 21 °C. On the other hand, a numerical model was developed using the specific heat capacity method, developed by Farid [102][56], and coupled to a building simulation program. The model could accurately predict the experimental measurements. Figure 9 compares the calculated and experimental results of the heat exchanger unit and the test cell performance during a four-day test, where the grey highlighted parts correspond to the peak demand period (6 p.m. to 8 p.m.).

Figure 8. PCM storage unit used for peak load shifting in Stathopoulos et al. study [101][55].

Figure 9. Numerical and experimental results for the PCM storage unit for peak load shifting over four days [101][55].

Using PCMs in underfloor heating is another method that can not only reduce electricity costs but also shift the heating load to off-peak hours. Devaux and Farid incorporated a PCM (melting range 27–29 °C) in an underfloor heating system in combination with another lower melting point PCM (21.7 °C) in the walls and ceiling of a 2.63 m × 2.64 m × 2.64 m hut. The results showed that the lower melting point PCM helped to maintain comfort condition, while the higher melting point PCM, in the underfloor heating system, created peak load shifting with energy and cost saving of 32% and 42%, respectively [103][57].

Table 4 shows the application of ON/OFF controller for peak load shifting in some other studies.

Table 4.

Application of ON/OFF controller in PCM-enhanced buildings used for peak load shifting.

2.2. Classical Control

P (Proportional), I (Integral), D (Derivative), PI (Proportional-Integral), PD(Proportional-Derivative), and PID (Proportional-Integral-Derivative) are the most commonly used classical controllers [70][23]. In process control, a correction is applied to a system based on the feedback received from the system. The action of the P controller is proportional to the difference between the set-point and the measured value [70][23]. The output of the I controller is proportional to the integral of the error with respect to time [117][71]. Finally, derivative control is the mode of control where the response is based on the derivative of the error with respect to time [118][72]. A PID controller, however, considers the features of all P, I, and D controllers, as shown in Figure 10. The advantage of classical controllers over ON/OFF controllers is their ability to adjust outputs to any values between 0% and 100%. Therefore, classical controllers are used when a stable and more precise control is required.

Figure 10.

The diagram of a Proportional-Integral-Derivative (PID) controller.

In terms of PCM-enhanced buildings, only three types of controllers were studied. Dehghan and Pfeiffer [119][73] carried out a numerical study to reduce the energy consumption of a building (retrofitted with PCM on its floor), while sustaining comfort. The building incorporated PCM in the underfloor heating system. A water tank charged by either solar energy during the daytime or an electric boiler during the night was used to pump the water into underfloor tubes. The surplus of solar energy was stored in the PCM for later use. In this regard, a thermostat having a built-in P controller was implemented to switch ON the electric boiler when solar energy was not enough to maintain the comfort condition. The results showed that the application of a control strategy enhanced the performance of the proposed system for space heating.

Wu et al. [120][74] coupled PCM storage with a heat pump to reduce the operating cost and energy consumption of a refrigeration system used to cool a building. A PI controller was used to control the expansion valve opening and hence maintain the superheat at the evaporator exit. A dynamic model was then constructed to consider the phase transitions within the heat pump’s heat exchangers and PCM storage tank. This mathematical model could successfully predict the experimental measurements. Buonomano et al. [121][75] developed a model in MATLAB to predict the energy demand of buildings equipped with PCM energy storage, PV/T collector, sunspace and smart daylighting systems. The model was developed based on the energy design of non-residential Nearly Zero Energy Buildings (NZEB) under Mediterranean weather conditions. A PI control scheme was used to find the optimal design for the location of PCM in building envelop, PV/T configuration and windows topology and hence minimize the heating and cooling demand of the building. The optimum design resulted in 17% energy saving.

In addition, through Transient systems- Computational fluid dynamics (TRNSYS-CFD), a simulation-based study (Figure 11), Gowreesunker et al. [122][76] evaluated the energy performance of a displacement ventilation system in the departure hall of an airport. The evaluation was performed by investigating the energy demand of a displacement ventilation diffuser retrofitted with a PCM heat exchanger and comparing it with that of the diffuser-only. A PID controller was also used to control the operation of HVAC system and hence maintain the comfort temperature of the hall between 18 °C and 23 °C. The results showed that the PCM storage improved the energy efficiency of the HVAC system for cooling more than heating (34% for cooling versus 22% for heating), and a maximum energy-saving of about 34% was achieved. Cabrol and Rowley [123][77] used the TRNSYS simulation tool for a domestic building to analyze the thermal benefits of a concrete floor embedded PCM, in combination with an air-source heat pump for creating peak load shifting. To this end, a building with the dimensions of 12 m × 10 m × 2.4 m was provided with underfloor heating controlled by a PID controller to sustain indoor thermal comfort (at 20 °C) over 360 h in different locations of UK. The control system was designed to use off-peak tariff options, and hence minimize the costs associated with the use of the heat pump. They reported that although incorporation of PCM enhances the thermal stability of a building, its selection depends on fabric construction of buildings.

Figure 11. The diagram of TRNSYS-CFD coupled simulation [122][76].

References

  1. Our World in Data. Global Fossil Fuel Consumption n.d. Available online: (accessed on 25 March 2021).
  2. International Energy Agency (AIE). Data and Statistics—Energy Consumption n.d. Available online: (accessed on 21 August 2020).
  3. Our World in Data. CO2 Emissions n.d. Available online: (accessed on 25 March 2021).
  4. U.S. Energy Information Administration (EIA). Total Energy—Annual Energy Review n.d. Available online: (accessed on 21 June 2019).
  5. Pérez-Lombard, L.; Ortiz, J.; Pout, C. A review on buildings energy consumption information. Energy Build. 2008, 40, 394–398.
  6. Barzin, R.; Chen, J.J.J.; Young, B.R.; Farid, M.M. Application of PCM energy storage in combination with night ventilation for space cooling. Appl. Energy 2015, 158, 412–421.
  7. U.S. Energy Information Administration (EIA). International Energy Statistics n.d. Available online: (accessed on 14 June 2019).
  8. Touretzky, C.R.; Salliot, A.A.; Lefevre, L.; Baldea, M. Optimal operation of phase-change thermal energy storage for a commercial building. Proc. Am. Control. Conf. 2015, 980–985.
  9. Kwok, A.G.; Grondzik, W.T. The green studio handbook: Environmental strategies for schematic design. Enq. A J. Archit. Res. 2007, 4.
  10. Goswami, D.Y.; Kreith, F. Handbook of Energy Efficiency and Renewable Energy; CRC Press: Boca Raton, FL, USA, 2007.
  11. Dincer, I.; Rosen, M. Thermal Energy Storage: Systems and Applications; John Wiley & Sons: Hoboken, NJ, USA, 2002.
  12. Li, G. Sensible heat thermal storage energy and exergy performance evaluations. Renew. Sustain. Energy Rev. 2016, 53, 897–923.
  13. Khudhair, A.M.; Farid, M.M. A review on energy conservation in building applications with thermal storage by latent heat using phase change materials. Energy Convers Manag. 2004, 45, 263–275.
  14. Pardo, P.; Deydier, A.; Anxionnaz-Minvielle, Z.; Rougé, S.; Cabassud, M.; Cognet, P. A review on high temperature thermochemical heat energy storage. Renew. Sustain. Energy Rev. 2014, 32, 591–610.
  15. Sharma, A.; Tyagi, V.V.; Chen, C.R.; Buddhi, D. Review on thermal energy storage with phase change materials and applications. Renew. Sustain. Energy Rev. 2009, 13, 318–345.
  16. Abedin, A.H.; Rosen, M.A. A critical review of thermochemical energy storage systems. Open Renew. Energy J. 2011, 4, 42–46.
  17. Jerz, J.; Simančík, F.; Španielka, J.; Šebek, J.; Kováčik, J.; Tobolka, P.; Dvorák, T.; Orovčík, L. Energy Demand Reduction in Nearly Zero-Energy Buildings by Highly Efficient Aluminium Foam Heat Exchangers. Mater. Sci. Forum 2018, 919, 236–245.
  18. Abhat, A. Low temperature latent heat thermal energy storage: Heat storage materials. Sol. Energy 1983, 30, 313–332.
  19. Cabeza, L.F.; Castell, A.; Barreneche, C.; De Gracia, A.; Fernández, A.I. Materials used as PCM in thermal energy storage in buildings: A review. Renew. Sustain. Energy Rev. 2011, 15, 1675–1695.
  20. Oró, E.; de Gracia, A.; Castell, A.; Farid, M.M.; Cabeza, L.F. Review on phase change materials (PCMs) for cold thermal energy storage applications. Appl. Energy 2012, 99, 513–533.
  21. Souayfane, F.; Fardoun, F.; Biwole, P.-H. Phase change materials (PCM) for cooling applications in buildings: A review. Energy Build. 2016, 129, 396–431.
  22. Merabti, S.; Draoui, B.; Bounaama, F. A review of control systems for energy and comfort management in buildings. In Proceedings of the 2016 8th International Conference on Modelling, Identification and Control (ICMIC), Algiers, Algeria, 15–17 November 2016; IEEE: New York, NY, USA, 2016; Volume 2017, pp. 478–486.
  23. Afram, A.; Janabi-Sharifi, F. Theory and applications of HVAC control systems—A review of model predictive control (MPC). Build. Environ. 2014, 72, 343–355.
  24. Gholamibozanjani, G.; Farid, M. Application of a Smart Control Strategy into a PCM-enhanced Building for Heating/Cooling Load Reduction. Energy Convers. Manag. 2020. under review.
  25. Solgi, E.; Kari, B.M.; Fayaz, R.; Taheri, H. The impact of phase change materials assisted night purge ventilation on the indoor thermal conditions of office buildings in hot-arid climates. Energy Build. 2017, 150, 488–497.
  26. Finck, C.; Beagon, P.; Claus, J.; Pean, T.; Vogler-Finck, P.; Zhang, K.; Kazmi, Z.H. Review of Applied and Tested Control Possibilities for Energy Flexibility in Buildings; KU Leuven Research Institute: Leuven, Belgium, 2018.
  27. Zumberge, J.; Passino, K.M. A case study in intelligent vs. conventional control for a process control experiment. Control Eng. Pract. 1998, 6, 1055–1075.
  28. Kenisarin, M.; Mahkamov, K. Passive thermal control in residential buildings using phase change materials. Renew. Sustain. Energy Rev. 2016, 55, 371–398.
  29. Treado, S.; Yan Chen, Y.C. Saving building energy through advanced control strategies. Energies 2013, 6, 4769–4785.
  30. Chen, X.; Zhang, Q.; Zhai, Z.J.; Ma, X. Potential of ventilation systems with thermal energy storage using PCMs applied to air conditioned buildings. Renew. Energy 2019, 138, 39–53.
  31. Sinka, M.; Bajare, D.; Jakovics, A.; Ratnieks, J.; Gendelis, S.; Tihana, J. Experimental testing of phase change materials in a warm-summer humid continental climate. Energy Build. 2019, 195, 205–215.
  32. Wang, N.; Liu, K.; Hu, J.H.; Wang, X.K. Simulation of operation performance of a solar assisted ground heat pump system with phase change thermal storage for heating in a rural building in Xi’an. IOP Conf. Ser. Earth Environ. Sci. 2019, 238.
  33. Szymocha, K. Advanced thermal solar system with heat storage for residential house space heating. In Proceedings of the SESCI 2005 Conference, British Columbia Institute of Technology, Burnaby, BC, Canada, 20–24 August 2005; Volume 24.
  34. Schossig, P.; Henning, H.-M.; Gschwander, S.; Haussmann, T. Micro-encapsulated phase-change materials integrated into construction materials. Sol. Energy Mater. Sol. Cells 2005, 89, 297–306.
  35. Shilei, L.V.; Neng, Z.; Guohui, F. Impact of phase change wall room on indoor thermal environment in winter. Energy Build. 2006, 38, 18–24.
  36. Medina, M.; Stewart, R. Phase-Change Frame Walls (PCFWs) for Peak Demand Reduction, Load Shifting, Energy Conservation and Comfort; Energy Systems Laboratory: College Station, TX, USA, 2008.
  37. Medina, M.; Zhu, D. A Comparative Heat Transfer Examination of Structural Insulated Panels (SIPs) with and without Phase Change Materials (PCMs) Using a Dynamic Wall Simulator; Energy Systems Laboratory: College Station, TX, USA, 2008.
  38. Medina, M.A.; King, J.B.; Zhang, M. On the heat transfer rate reduction of structural insulated panels (SIPs) outfitted with phase change materials (PCMs). Energy 2008, 33, 667–678.
  39. Muruganantham, K.; Phelan, P.; Horwath, P.; Ludlam, D.; McDonald, T. Experimental investigation of a bio-based phase change material to improve building energy performance. Energy Sustain. 2010, 43949, 979–984.
  40. Jaworski, M.; Łapka, P.; Furmanski, P. Numerical modelling and experimental studies of thermal behaviour of building integrated thermal energy storage unit in a form of a ceiling panel. Appl. Energy 2014, 113, 548–557.
  41. Zhou, Y.; Zheng, S.; Zhang, G. Study on the energy performance enhancement of a new PCMs integrated hybrid system with the active cooling and hybrid ventilations. Energy 2019, 179, 111–128.
  42. Zhou, Y.; Yu, C.W.F.; Zhang, G. Study on heat-transfer mechanism of wallboards containing active phase change material and parameter optimization with ventilation. Appl. Therm. Eng. 2018, 144, 1091–1108.
  43. Bimaganbetova, M.; Memon, S.A.; Sheriyev, A. Performance evaluation of phase change materials suitable for cities representing the whole tropical savanna climate region. Renew. Energy 2020, 148, 402–416.
  44. Han, Z.; Zheng, M.; Kong, F.; Wang, F.; Li, Z.; Bai, T. Numerical simulation of solar assisted ground-source heat pump heating system with latent heat energy storage in severely cold area. Appl. Therm. Eng. 2008, 28, 1427–1436.
  45. Marin, P.; Saffari, M.; De Gracia, A.; Zhu, X.; Farid, M.M.; Cabeza, L.F.; Ushak, S. Energy savings due to the use of PCM for relocatable lightweight buildings passive heating and cooling in different weather conditions. Energy Build. 2016, 129, 274–283.
  46. Shan, K.; Wang, S.; Yan, C.; Xiao, F. Building demand response and control methods for smart grids: A review. Sci. Technol. Built Environ. 2016, 22, 692–704.
  47. Barzin, R.; Chen, J.J.; Young, B.R.; Farid, M.M. Application of PCM underfloor heating in combination with PCM wallboards for space heating using price-based control system. Appl. Energy 2015, 148, 39–48.
  48. Sun, Y.; Wang, S.; Xiao, F.; Gao, D. Peak load shifting control using different cold thermal energy storage facilities in commercial buildings: A review. Energy Convers. Manag. 2013, 71, 101–114.
  49. Sadineni, S.B.; Boehm, R.F. Measurements and simulations for peak electrical load reduction in cooling dominated climate. Energy 2012, 37, 689–697.
  50. Bourne, S.; Novoselac, A. Compact PCM-based thermal stores for shifting peak cooling loads. Build. Simul. 2015, 8, 673–688.
  51. Khudhair, A.M.; Farid, M.M. Use of phase change materials for thermal comfort and electrical energy peak load shifting: Experimental investigations. In Proceedings ISES World Congrress 2007; ISES: Freiburg, Germany, 2008; Volume I–V, pp. 283–288.
  52. Bastani, A.; Haghighat, F.; Manzano, C.J. Investigating the effect of control strategy on the shift of energy consumption in a building integrated with PCM wallboard. Energy Procedia 2015, 78, 2280–2285.
  53. Barzin, R.; Chen, J.J.; Young, B.R.; Farid, M.M. Peak load shifting with energy storage and price-based control system. Energy 2015, 92, 505–514.
  54. Lazaro, A.; Dolado, P.; Marín, J.M.; Zalba, B. PCM-air heat exchangers for free-cooling applications in buildings: Experimental results of two real-scale prototypes. Energy Convers. Manag. 2009, 50, 439–443.
  55. Stathopoulos, N.; El Mankibi, M.; Issoglio, R.; Michel, P.; Haghighat, F. Air-PCM heat exchanger for peak load management: Experimental and simulation. Sol. Energy 2016, 132, 453–466.
  56. Farid, M.M. A new approach in the calculation of heat transfer with phase change. In Proceedings of the 9th International Congress of Energy and Environment, Miami, FL, USA, 11–13 December 1989; pp. 1–19.
  57. Devaux, P.; Farid, M.M. Benefits of PCM underfloor heating with PCM wallboards for space heating in winter. Appl. Energy 2017, 191, 593–602.
  58. Lin, K.; Zhang, Y.; Di, H.; Yang, R. Study of an Electrical Heating System with Ductless Air Supply and Shape-Stabilized PCM for Thermal Storage. Energy Convers. Manag. 2007, 48, 2016–2024.
  59. Real, A.; Garcia, V.G.; Domenech, L.; Renau, J.; Montés, N.; Sanchez, F.P. Improvement of a Heat Pump Based HVAC System with PCM Thermal Storage for Cold Accumulation and Heat Dissipation. Energy Build. 2014, 83, 108–116.
  60. Hirmiz, R.; Teamah, H.; Lightstone, M.; Cotton, J. Performance of Heat Pump Integrated Phase Change Material Thermal Storage for Electric Load Shifting in Building Demand Side Management. Energy Build. 2019, 190, 103–118.
  61. Mazo, J.; Delgado, M.; Marin, J.M.; Zalba, B. Modeling a Radiant Floor System with Phase Change Material (PCM) Integrated into a Building Simulation Tool: Analysis of a Case Study of a Floor Heating System Coupled to a Heat Pump. Energy Build. 2012, 47, 458–466.
  62. Qureshi, W.A.; Nair, N.-K.C.; Farid, M.M. Impact of Energy Storage in Buildings on Electricity Demand Side Management. Energy Convers. Manag. 2011, 52, 2110–2120.
  63. Hong, T.; Wang, S.; Wang, F.; Wang, X. Experimental Study on the Demand Shifting Effects of PCM Integrated Air-Conditioning Duct. IOP Conf. Ser. Earth Environ. Sci. 2019, 238, 012048.
  64. Hong, T.; Wang, S.; Wang, F.; Wang, X. Study on the Optimization of PCM Integrated Air-Conditioning Duct for the Demand Shifting. IOP Conf. Ser. Earth Environ. Sci. 2019, 238, 12045.
  65. Faraj, K.; Faraj, J.; Hachem, F.; Bazzi, H.; Khaled, M.; Castelain, C. Analysis of Underfloor Electrical Heating System Integrated with Coconut Oil-PCM Plates. Appl. Therm. Eng. 2019, 158.
  66. Cunha, J.P.; Eames, P.C. The Potential of Phase Change Energy Storage for Office Cooling Load Shifting. IOP Conf. Series: Mater. Sci. Eng. 2019, 556, 12058.
  67. Teamah, H.; Lightstone, M. Numerical Study of the Electrical Load Shift Capability of a Ground Source Heat Pump System with Phase Change Thermal Storage. Energy Build. 2019, 199, 235–246.
  68. Sun, W.; Zhang, Y.; Ling, Z.; Fang, X.; Zhang, Z. Experimental Investigation on the Thermal Performance of Double-Layer PCM Radiant Floor System Containing Two Types of Inorganic Composite PCMs. Energy Build. 2020, 211, 109806.
  69. Gholamibozanjani, G.; Farid, M. Peak Load Shifting Using a Price-Based Control in PCM-Enhanced Buildings. Sol. Energy 2020, 211, 661–673.
  70. Gholamibozanjani, G.; Farid, M. A Comparison Between Passive and Active PCM Systems Applied to Buildings. Renew. Energy 2020, 162, 112–123.
  71. Kanellakopoulos, I.; Krein, P.T. Integral-Action Nonlinear Control of Induction Motors. IFAC Proc. Vol. 1993, 26, 117–120.
  72. Boros, V. A Digital Proportional, Integral and Derivative Feedback Controller for Power Conditioning Equipment; Institute of Electrical and Electronics Engineers (IEEE): New York, NY, USA, 1977; pp. 135–141.
  73. Dehghan, M.; Pfeiffer, C. Modelling and Control of Collecting Solar Energy for Heating Houses in Norway. J. Sustain. Dev. Energy Water Environ. Syst. 2017, 5, 359–376.
  74. Wu, J.; Tremeac, B.; Terrier, M.-F.; Charni, M.; Gagnière, E.; Couenne, F.; Hamroun, B.; Jallut, C. Experimental Investigation of the Dynamic Behavior of a Large-Scale Refrigeration–PCM Energy Storage System. Validation of a Complete Model. Energy 2016, 116, 32–42.
  75. Buonomano, A.; De Luca, G.; Montanaro, U.; Palombo, A. Innovative Technologies for NZEBs: An Energy and Economic Analysis Tool and a Case Study of a Non-Residential Building for the Mediterranean Climate. Energy Build. 2016, 121, 318–343.
  76. Gowreesunker, B.; Tassou, S.; Kolokotroni, M. Coupled TRNSYS-CFD Simulations Evaluating the Performance of PCM Plate Heat Exchangers in an Airport Terminal Building Displacement Conditioning System. Build. Environ. 2013, 65, 132–145.
  77. Cabrol, L.; Rowley, P. Towards Low Carbon Homes—A Simulation Analysis of Building-Integrated Air-Source Heat Pump Systems. Energy Build. 2012, 48, 127–136.